Description: XPOLE PL7 C2/3 ( MOELLER
)
MOELLER XPOLE PL7 C2/3 Circuit-breaker
Product Name: MOELLER XPOLE PL7 C2/3 Circuit-breaker
Product Brand: MOELLER
Product Code: XPOLE PL7 C2/3
Product Artikel: Catalog No. 263404
Technical data Electrical Rated switching capacity according to IEC/EN 60898-1 Icn kA
10 Design verification as per IEC/EN 61439 Technical data for design verification Rated operational current for specified heat dissipation In
A 2 Heat dissipation per pole, current-dependent Pvid W 0 Equipment heat dissipation, current-dependent Pvid W 4.1 Static heat dissipation, non-current-dependent Pvs W 0 Heat dissipation capacity Pdiss W 0 Operating ambient temperature min. °C -25 Operating ambient temperature max. °C 75 linear, per +1 °C, results in a 0.5% reduction of current
carrying capacity IEC/EN 61439 design verification 10.2 Strength of materials and parts 10.2.2 Corrosion resistance Meets the product standard's
requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets
the product standard's requirements. 10.2.3.2 Verification of resistance of insulating materials
to normal heat Meets the product standard's requirements. 10.2.3.3 Verification of resistance of insulating materials
to abnormal heat and fire due to internal electric effects Meets the product standard's requirements. 10.2.4 Resistance to ultra-violet (UV) radiation Meets the
product standard's requirements. 10.2.5 Lifting Does not apply, since the entire switchgear
needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire
switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard's
requirements. 10.3 Degree of protection of ASSEMBLIES Does not apply,
since the entire switchgear needs to be evaluated. 10.4 Clearances and creepage distances Meets the product
standard's requirements. 10.5 Protection against electric shock Does not apply, since
the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does
not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the
panel builder's responsibility. 10.8 Connections for external conductors Is the panel
builder's responsibility. 10.9 Insulation properties 10.9.2 Power-frequency electric strength Is the panel
builder's responsibility. 10.9.3 Impulse withstand voltage Is the panel builder's
responsibility. 10.9.4 Testing of enclosures made of insulating material Is
the panel builder's responsibility. 10.10 Temperature rise The panel builder is responsible for
the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder's
responsibility. The specifications for the switchgear must be observed. 04/24/2020 Eaton 263404 ED2020 V67.0 EN 1 / 2 10.12 Electromagnetic compatibility Is the panel builder's
responsibility. The specifications for the switchgear must be observed. 10.13 Mechanical function The device meets the requirements,
provided the information in the instruction leaflet (IL) is observed. Technical data ETIM 7.0 Circuit breakers and fuses (EG000020) / Miniature circuit
breaker (MCB) (EC000042) Electric engineering, automation, process control
engineering / Electrical installation, device / Miniature circuit breaker
system (MCB) / Miniature circuit breaker (MCB) (ecl@ss10.0.1-27-14-19-01 [AAB905014]) Release characteristic C Number of poles (total) 3 Number of protected poles 3 Rated current A 2 Rated voltage V 400 Rated insulation voltage Ui V 440 Rated impulse withstand voltage Uimp kV 4 Rated short-circuit breaking capacity Icn EN 60898 at 230 V
kA 10 Rated short-circuit breaking capacity Icn EN 60898 at 400 V
kA 10 Rated short-circuit breaking capacity Icu IEC 60947-2 at 230
V kA 0 Rated short-circuit breaking capacity Icu IEC 60947-2 at 400
V kA 0 Voltage type AC Frequency Hz 50 - 60 Current limiting class 3 Suitable for flush-mounted installation No Concurrently switching N-neutral No Over voltage category 3 Pollution degree 2 Additional equipment possible Yes Width in number of modular spacings 3 Built-in depth mm 70.5 Degree of protection (IP) IP20 Ambient temperature during operating °C -25 - 55 Connectable conductor cross section multi-wired mm² 1 - 25
Connectable conductor cross section solid-core mm² 1 - 25