industrialmaterialcenter.com

Janitza UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer

Janitza

Product number: UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer
Producer: Janitza
Confirmed Rating: ☆☆☆☆☆ ()
Rating Count:

You can fill in the online quotation form or get in touch with Live Support Team for the Janitza brand, UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer product. We will get back to you as soon as possible.
PLEASE MAIL TO: info@industrialmaterialcenter.com

Datasheets for Janitza UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer

Description for Janitza UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer

Power qualityHarmonics analysis up to the 63rd harmonic, even / odd (U, I, P, Q)Interharmonics (U, I)Distortion factor THD-U / THD-I / TDDMeasurement of positive, negative and zero sequence componentUnbalanceDirection of rotation fieldVoltage crest factorFlicker measurement in accordance with DIN EN 61000-4-15Logging and storage of transients (> 39 µs)Short-term interruptions (> 10 ms)Monitoring start-up processesHigh quality measurementConstant true RMS measurementMeasurement process in accordance with IEC 61000-4-30Certified accuracy of measurement according to class AContinuous sampling of the voltage and current measurement inputs at 25,6 kHz512 measurement points per periodRecording of over 2,000 measured values per measurement cycleAccuracy of active energy measurement: Class 0.2SFast measurement even enables the logging of rapid transients from 39 µsLogging of currents and voltages (15 – 440 Hz)User-friendly, colour graphical display with intuitive user guidanceHigh resolution colour graphical display 320 x 240, 256 colours, 6 buttonsUser-friendly, self-explanatory and intuitive operationBacklight for optimum reading, even in darker environmentsIllustration of measured values in numeric form, as a bar graph or line graphClear and informative representation of online graphs and power quality eventsMultilingual: German, English, Russian, Spanish, Chinese, French, Turkish ...RCM (Residual Current Monitoring)Continuous monitoring of residual currents (Residual Current Monitor, RCM)Alarming in case a preset threshold fault current reachedNear-realtime reactions for triggering countermeasuresPermanent RCM measurement for systems in permanent operation without the opportunity to switch offIdeal for the central earthing point in TN-S systemsBACnet protocol for building communicationOptimal interoperability between devices from various manufacturersPredefined BIBBs (BACnet Interoperability Building Block)BACnet is optionally available with UMG 512-PROUMG 512-PRO supports the device type B-SA with the BIBBs DS-RP-B and DS-WP-BFurthermore, the BIBBs DS-COV-B and DM-UTC-B are also supportedComprehensive communication and connection possibilities4 voltage and 6 current measurement inputs2 digital inputs, e.g. as data logger for S0 meter2 digital outputs for alarm message or e.g. for connection to a BMS or PLCFree name assignment for the digital IOs, e.g. if used as data loggerModbusProfibusEthernet (TCP/IP)Digital IOsBACnet (optional)Configurable FirewallModern communications architecture via EthernetSimple integration in an Ethernet networkReliable and cost-optimised establishment of communicationIdeal for Master-Slave structuresHigh flexibility due to the use of open standardsIntegration in PLC systems and BMS through additional interfacesVarious IP protocols: SNMP, ICMP (Ping), NTP, FTP …Up to 4 ports simultaneousProgramming / PLC functionalityFurther processing of the measurement data in the measuring device (local intelligence)Monitoring and alarm functions simple to programSustainable functional expansions far beyond pure measurementComprehensive programming options with Jasic® source code programmingGraphical programmingComplete APPs from the Janitza libraryLarge measurement data memory256 MB data memoryMemory range up to 2 years (configuration-dependent)Individually configurable recordingsRecording averaging times can be freely selectedPQ recordings template preconfigured for conventional standards (e.g. EN 50160)User-defined memory segmenting possiblePowerful alarm managementInformation available immediately by emailInform maintenance personnel via the powerful device homepageVia digital outputs, Modbus addresses, GridVis® softwareProgramming via Jasic® or graphical programmingFurther alarm management functions via GridVis®-Service alarm managementPeak load representation and peak load managementIllustration of the 3 highest monthly power peaks on the LCD display (P, Q, S)Rolling bar chart representation of the peak power values over 3 years on the LCD display (P, Q, S)Plain text representation on the LCD display (P)

Latest Comments for Janitza UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer


Other Recommended Products Janitza


Janitza UMG 96 S 5213017 Power Analyzer
Janitza UMG 96-PA, 90-277V Energy Meter
Janitza UMG 96RM Power Analyzer
Janitza UMG 96 RM-E (52.22.062) Multifunctional Network Analyzer
Janitza UMG 96 Analyzer
Janitza UMG 604 E-PRO 230V (UL) Power Analyzer
Janitza UMG 512-PRO 95 ... 240 V AC, 80 ... 300 V DC Power Quality Analyzer
Janitza UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer
Janitza UMG 509-PRO UH= 95-240V AC Analyzer
Janitza UMG 508 95/240V AC Power Analyzer
Janitza UMG 103-CBM 240 / 415 V AC Universal Measuring Design
Janitza UMG 103-CBM Universal Measuring Device
Janitza Prophi 52.08.008 Reactive Power Controller
Janitza Prophi 12R Reactive Power Controller
Janitza 96RM-CBM 90/277V AC Power Analyzer
Janitza 96 RM-EL Power Analyzer Or Technically Equivalent
Janitza 5222064 Energy Meter With Profibus
Janitza 5222063 Energy Measuring Device