Janitza UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer
Janitza
Ürün No: UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer
Üretici: Janitza
Confirmed Rating:
☆☆☆☆☆ ()
Rating Count:
Janitza markalı, UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer koduna sahip Janitza UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer isimli ürün hakkında detaylı bilgi almak için lütfen canlı destek ekibimiz ile hemen iletişime geçin ya da bir online teklif formu doldurun. Size en kısa sürede dönüş yapacağız.
PLEASE MAIL TO: info@industrialmaterialcenter.com
Datasheets for Janitza UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer
Description for Janitza UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer
Power qualityHarmonics analysis up to the 63rd harmonic, even / odd (U, I, P, Q)Interharmonics (U, I)Distortion factor THD-U / THD-I / TDDMeasurement of positive, negative and zero sequence componentUnbalanceDirection of rotation fieldVoltage crest factorFlicker measurement in accordance with DIN EN 61000-4-15Logging and storage of transients (> 39 µs)Short-term interruptions (> 10 ms)Monitoring start-up processesHigh quality measurementConstant true RMS measurementMeasurement process in accordance with IEC 61000-4-30Certified accuracy of measurement according to class AContinuous sampling of the voltage and current measurement inputs at 25,6 kHz512 measurement points per periodRecording of over 2,000 measured values per measurement cycleAccuracy of active energy measurement: Class 0.2SFast measurement even enables the logging of rapid transients from 39 µsLogging of currents and voltages (15 – 440 Hz)User-friendly, colour graphical display with intuitive user guidanceHigh resolution colour graphical display 320 x 240, 256 colours, 6 buttonsUser-friendly, self-explanatory and intuitive operationBacklight for optimum reading, even in darker environmentsIllustration of measured values in numeric form, as a bar graph or line graphClear and informative representation of online graphs and power quality eventsMultilingual: German, English, Russian, Spanish, Chinese, French, Turkish ...RCM (Residual Current Monitoring)Continuous monitoring of residual currents (Residual Current Monitor, RCM)Alarming in case a preset threshold fault current reachedNear-realtime reactions for triggering countermeasuresPermanent RCM measurement for systems in permanent operation without the opportunity to switch offIdeal for the central earthing point in TN-S systemsBACnet protocol for building communicationOptimal interoperability between devices from various manufacturersPredefined BIBBs (BACnet Interoperability Building Block)BACnet is optionally available with UMG 512-PROUMG 512-PRO supports the device type B-SA with the BIBBs DS-RP-B and DS-WP-BFurthermore, the BIBBs DS-COV-B and DM-UTC-B are also supportedComprehensive communication and connection possibilities4 voltage and 6 current measurement inputs2 digital inputs, e.g. as data logger for S0 meter2 digital outputs for alarm message or e.g. for connection to a BMS or PLCFree name assignment for the digital IOs, e.g. if used as data loggerModbusProfibusEthernet (TCP/IP)Digital IOsBACnet (optional)Configurable FirewallModern communications architecture via EthernetSimple integration in an Ethernet networkReliable and cost-optimised establishment of communicationIdeal for Master-Slave structuresHigh flexibility due to the use of open standardsIntegration in PLC systems and BMS through additional interfacesVarious IP protocols: SNMP, ICMP (Ping), NTP, FTP …Up to 4 ports simultaneousProgramming / PLC functionalityFurther processing of the measurement data in the measuring device (local intelligence)Monitoring and alarm functions simple to programSustainable functional expansions far beyond pure measurementComprehensive programming options with Jasic® source code programmingGraphical programmingComplete APPs from the Janitza libraryLarge measurement data memory256 MB data memoryMemory range up to 2 years (configuration-dependent)Individually configurable recordingsRecording averaging times can be freely selectedPQ recordings template preconfigured for conventional standards (e.g. EN 50160)User-defined memory segmenting possiblePowerful alarm managementInformation available immediately by emailInform maintenance personnel via the powerful device homepageVia digital outputs, Modbus addresses, GridVis® softwareProgramming via Jasic® or graphical programmingFurther alarm management functions via GridVis®-Service alarm managementPeak load representation and peak load managementIllustration of the 3 highest monthly power peaks on the LCD display (P, Q, S)Rolling bar chart representation of the peak power values over 3 years on the LCD display (P, Q, S)Plain text representation on the LCD display (P)
Latest Comments for Janitza UMG 512-PRO 48 ... 110 V AC, 24 ... 150 V DC Power Quality Analyzer
İlginizi Çekebilecek Ürünler Janitza