Zpa Pecky MO EEx Electric Actuator
Zpa Pecky
Ürün No: MO EEx
Üretici: Zpa Pecky
Confirmed Rating:
☆☆☆☆☆☆
(4.2)
Rating Count: 3792
Zpa Pecky markalı, MO EEx koduna sahip Zpa Pecky MO EEx Electric Actuator isimli ürün hakkında detaylı bilgi almak için lütfen canlı destek ekibimiz ile hemen iletişime geçin ya da bir online teklif formu doldurun. Size en kısa sürede dönüş yapacağız.
PLEASE MAIL TO: info@industrialmaterialcenter.com
Datasheets for Zpa Pecky MO EEx Electric Actuator
Description for Zpa Pecky MO EEx Electric Actuator
The MODACT® MO EEx electric rotary multi-turn actuators are specially intended for controlling devices by a reversing rotary motion, e.g. slide valves and valves, and, in connection with an appropriate gearbox, also flap or ball valves, and other devices for which they are suitable due to their properties.They can be operated in an environment with a danger of explosion of explosive gaseous atmosphere in zone 1 and zone 2 according to EN 60079-10 (332320). The actuators are designed as a device of group II, category 2G in compliance with standards EN 60079-0:2004, EN 60079-1:2004, and EN 60079-7:2004 for explosive gaseous atmosphere.The actuators are marked with a label of protection against explosion and symbols of the group and category of the device Ex II 2G or Ex I M2; in addition, according to version for surrounding temperature -25°C to + 55°C with marking Ex de IIC T4 or for surrounding temperature -50°C to +55°C with marking Ex de IIB T4, and/or as modification for using in mines of group I, category M2 with marking Ex de I (see chapter Data on actuators).Technical dataMO EExType number521205212152122521235212452125 20-12563-160160-250250-500320-630630-1100Tripping force [kN] Adjusting time [s/90°] Position-changing velocity[min-1]11-4016-12510-8016-10016-6330-100[mm/min] Working stroke[°] [ot]2-250 (2-620)2-250 (2-620)2-250 (2-620)2-240 (2-470)2-240 (2-470)2-240 (2-470)[mm] Supply voltage1x 230 V, 50 Hz 24 V, 50 Hz 1 x 110 V, 50 Hz 3 x 230 / 400 V, 50 Hz✔✔✔✔✔✔ControlTwo position On-Off✔✔✔✔✔✔Three position Continuous PROFIBUS Position sensingResistance transmitter (R)✔✔✔✔✔✔Absolute✔✔✔✔✔✔Current transmitter (I)✔✔✔✔✔✔Position interrupt✔✔✔✔✔✔Torque-initated interrupt✔✔✔✔✔✔Manual actuation✔✔✔✔✔✔Explosion-proof design✔✔✔✔✔✔Type of enclosureIP 55IP 55IP 55IP 55IP 55IP 55Weight - depending on design (Al/cast iron) and on motor [kg]47-4957-8057-80112-150108-150239-248UsageDesignation of explosion-proof propertiesIt consists of the following symbols:EEx - Electric device complies with the standard EN 50 014 and related standards for various types of protection against explosion.d - Designation of the type of protection against explosion, explosion-proof closure according to EN 50 018.II - Designation of the group of explosion-proof electric device according to ČSN EN 50 014.C - Designation of the sub-group of the group of explosion-proof electric device according to EN 50 014.T4 - Designation of temperature class of explosion-proof electric device of the Group II according to EN 50 014.NomenclatureEnvironment with explosion danger - environment in which an explosive atmosphere can be createdExplosive gaseous atmosphere - a mixture of flammable substances (in the form of gases, vapours or mist) with air under atmospheric conditions in which, after initialization, burning spreads out to non-consumed mixture.Maximum surface temperature - The highest temperature created during operation under the most unfavourable conditions (however within approved limits) on any surface part of the electric device, which could induce ignition of surrounding atmosphere.Closure - All walls, doors, covers, cable bushings, shafts, rods, pull-rods, etc. which contribute to the type of protection against explosion and/or to the level of protection (IP) of the electric device.Explosion-proof closure “d” - Type of protection in which the parts capable of causing ignition of an explosive atmosphere are installed inside the closure; in case of internal explosion this closure should withstand pressure of the explosion and prevent spreading of the explosion into the surrounding atmosphere.Secured design “e” - Type of protection against explosion with additional measures adopted for increased safety against non-permissible temperature increase and formation of sparks or arcs inside and on external parts of the electric device which, under normal operating conditions, does not form sparks or arcs.
Latest Comments for Zpa Pecky MO EEx Electric Actuator
İlginizi Çekebilecek Ürünler Zpa Pecky