LEROY SOMER SP 2,5 T

使用产品代码 SP 2,5 T 访问产品#LEROY SOMER 的库存,交货和价格信息。 LEROY, SOMER, LEROY SOMER, SP, LEROY SP, SOMER SP, LEROY SOMER SP, 2,5, LEROY 2,5, SOMER 2,5, LEROY SOMER 2,5
产品编号 SP 2,5 T
生产厂家 LEROY SOMER

Description: SP 2,5 T ( LEROY SOMER )

LEROY SOMER SP 2,5 T



Product Name: LEROY SOMER SP 2,5 T
Product Brand: LEROY SOMER
Product Code: SP 2,5 T
Product Artikel: LEROY SOMER SP 2,5 T
It is recommended that the internal EMC filter be kept in place unless there is a specific reason for removing it. If the drive is part of a regen system or is a Unidrive SP size 3 to 6 on an IT supply then the internal EMC filter must be removed. The internal EMC filter reduces radio-frequency emission into the line power supply. Where the motor cable is short, it permits the requirements of EN61800-3:2004 to be met for the second environment - for further information see the Unidrive SP User Guide. For longer motor cables the filter continues to provide a useful reduction in emission level, and when used with any length of shielded motor cable up to the limit for the drive, it is unlikely that nearby industrial equipment will be disturbed. It is recommended that the filter be used in all applications unless the ground leakage current (on 400V, 50Hz supply) of 28mA for sizes 0 to 3 and 56mA for sizes 4 to 6 is unacceptable or the above conditions are true. Figure 3-5 Removal of SPz internal EMC filter